2.8.10               Air Intake Valves

 

                        The air intake valves shall be spring loaded or check type and be provided/mounted on fly ash branch pipe for air entry as may be re­quired for necessary assistance to ensure the ash extraction. The exact number and size shall be as per system requirement. The valve body shall be made of Cast Iron/Gun Metal/Cast Steel and disc shall be constructed of SS or Gun Metal.  All air intake valves shall be provided with suitable rain-hood protection.

 