Spec Ash Handling Plant

December 26, 2008

2.8.14 Fittings & PIPES

Filed under: AHP, thermal power plant — Tags: , , , — shivajichoudhury @ 6:38 am

2.8.14               Fittings

 

                        All fly ash conveying line fittings i.e. bends, elbows, laterals and spool pieces shall be alloy cast iron or basalt lined fittings. These shall be either flanged or plain end fittings.

 

                        All the fittings (bends, elbows/laterals spool pieces etc.) in the conveying lines shall be as per good Engg. practice and of large radius construction (min. 5D).

 

                        Alloy C.I or basalt lined (as the case may be) spool pieces of minimum 1.5 m length shall be provided at the discharge of every bend or lateral, which shall be directly welded to the bends/laterals or joined with either a flanged connection or a sleeve coupling with the bends/elbows.

 

                        Material of construction and other design parameters of the piping are as follows:

 

Pipe size (I.D.)

As required.

Type of Pipes

Class-D cast iron pipes conforming to IS:1536 or BS:1211.

Type of Joints

 

Pipe to Pipe, Pipe to Fitting, Pipe to valve & valve to Fitting, Fitting to Fitting,

Flanged/sleeve coupling

Fittings (Bends, elbows laterals and spool piece etc.),

Ni-hard/chrome-alloy cast iron or equivalent.  Minimum hardness 400 BHN. and wear back thickness minimum 20 mm.     or

 

20 MM thk. Cast basalt lined MS fittings (MS sheet of 6 mm thickness)

Basalt Lining

 

Hardness

8 mhos (Min.)

Bending strength

300 Kg/cm2 (Min.)

Compressive strength

4500 Kg/cm2 (Min.)

Density

2.8 – 2.9 Kg/cm3

Sleeve Couplings

 

Material of Construction

 

(a) Sleeve

9.0 mm thick carbon steel ASTM-36/BS EN 10025: :1993 Grade S:275/355 or CI FG 260:IS:210

(b) Flanges/End rings

Carbon steel to ASTM –A-108/Cast IRON FG-260, IS:210 steel and rings shall be formed from hot rolled sect welds.

(c) Gasket

: To suit ash temperature

Material                                                  Nitrile (NBR) BS:2494 Grade G/Neoprene

 

Nuts & Bolts

Hot dip galvanised as per IS:4759. Bolts, nuts and washer should be of similar material to those used for coupling housing/sleeves to minimise the possibility of galvanic corrosion.

 

December 23, 2008

2.8.15 Surge/ Buffer Hoppers

Filed under: AHP, thermal power plant — shivajichoudhury @ 5:41 am

2.8.15               Surge/ Buffer Hoppers

 

                        Fly ash from the various collection chutes/hoppers of each unit shall be conveyed to buffer/surge hopper, four nos. for each unit.  The minimum effective storage capacity of buffer hopper shall be 10 minutes storage of extraction stream capacity. The bottom portion of the buffer/surge hopper  shall be of conical shape.  Aeration pads shall be provided in the conical portion of buffer hopper to prevent compaction and to fluidize the fly ash during discharge from the buffer hopper.

 

                        Buffer/surge hoppers are to discharge the fly ash extracted from various fly ash collection chutes to pressure transporter system in case of vacuum/pressure extraction system and pressure transportation system.

 

                        Each hopper shall be constructed by 10 mm thick MS plate as per IS 2062 with 10 mm thick abrasion resistant alloy cast iron liners of 300 – 350 BHN hardness at sloping surfaces and outlet area..  Each hopper shall include an access door.  Circular doors shall have a diameter not less than 750 mm, whilst rectangular doors shall have dimensions of at least 750 mm x 750 mm.

 

                        Pressure relief valves to atmosphere from the buffer/surge hoppers are prohibited.

 

                        In order to prevent contaminated air being entering into vacuum pump, 1×100% capacity bag filters shall be provided on buffer/surge hopper.

 

2.8.15.1            Instruments

 

                        Each buffer/surge hopper shall be provided with following instruments as a minimum.

 

a)         Hopper ash level switches                       High                 :           1 No.

                                                                        Low                 :           1 No.   

 

b)         Pressure gauge at the transport

            air inlet line                                                                   :           1 No.

 

c)         Pressure switches at the                         High – High       :           1 No.

            transport air inlet line                              High                 :           1 No.

                                                                        Low                 :           1 No.

                                                                        Low – Low        :           1 No.   

           

d)         Differential pressure gauge

            across the bag filter                                                        :           1 No.

 

e)         Differential pressure switch

            across the bag filter                                                        :           1 No.

 

f)          Pressure or Vacuum gauge with

            bag filter depending on pressure

            or vacuum extraction system                                           :           1 No.

 

g)         Pressure gauge at each of

            the fluidising air inlet line                                                :           1 No.

 

h)         Temperature gauge at each of

            the fluidising air inlet line                                                :           1 No.

 

i)          Vacuum gauge in each of the

            vacuum line to vacuum pump                                         :           1 No.

 

j)          Vacuum switch in each of the                 High – High       :           1 No.

            vacuum line to vacuum pump                 High                 :           1 No.

                                                                        Low                 :           1 No.

                                                                        Low – Low        :           1 No.   

 

December 3, 2008

2.8.16 Air Compressors for Pneumatic Conveying of Ash

Filed under: thermal power plant — Tags: — shivajichoudhury @ 7:01 am

2.8.16               Air Compressors for Pneumatic Conveying of Ash

                       

                        Air compressors shall be designed for continuous opera­tion with high efficiency to satisfy the system re­quirements.  Satisfactory operation in parallel shall be ensured without any uneven load sharing, undue vibration, noise etc.

 

                        The design shall incorporate every reasonable precau­tion for the safety of all operation and maintenance personnel.  Each compressor unit should have all moving parts protected by a guard.

 

                        The scope of supply shall include all the necessary compressed air system complete with compressors, coolers, necessary isolating and non return valves, pressure relief valve, water separators, silencers and vent pipe work, which shall be ducted to a safe dis­charge outlet.

 

                        For second stage conveying (i.e. for transportation of ash from surge/buffer hoppers to main storage silos)

                       

                        (a)        Three (3) nos. ash transportation lines (i.e. two (2) working + one (1) standby shall be provided for each unit.

 

                        (b)        3×50% capacity compressors shall be provided. 

 

                        (c)        The capacity of transport air compressors shall be decided to match the capacity of extraction system i.e. the capacity of extraction and transportation system shall be similar.

 

                        The output from each set of working compressors (as applicable), expressed as free air delivered (FAD) at ambient conditions, shall be as indicated in accompany data-sheet.  At least 10% margin shall be provided on compressor capacity over and above the maximum flow requirement. 50 Degree C ambient and a RH of 100% shall be considered for design of capacity of compressors.

 

                        Compressors shall be screw type.  All air compressors and their drives provided under this contract for a particular duty.

 

                        The compressed air in contact with the fly ash shall not contain oil exceeding 5 ppm.  Therefore, oil injected compressors should be provided with associated oil separators to ensure oil not exceeding 5 ppm in compressed air system.  Another essential requirement is for ‘dryness’ of the com­pressed air, and to achieve it, bidders shall offer a compressed air system which includes a moisture remov­al system. This system should comprise of a refrigeration type dryer.

 

                        Each compressor shall have an inlet filter of dry type to protect the compressor.  The filter inlet area should be large enough to ensure frequent filter changes are not required.

 

                        A crank shaft driven positive displacement lubricating pump shall be used for lubricating the bearings and any other parts needing lubrication.

 

                        Cooling water requirement, if any, shall be arranged by the bidder.

 

Bidder shall include an inlet and/or outlet silencer so that each compressor unit complies with the noise requirements.

 

2.8.16.1            Air Receivers

 

                        Each compressor shall be provided with an air receiver of ample size of so that delivered air pressure is kept within ± 5% of rated pressure without excessive start/stop operation in the working cycle.

 

                        Air receivers shall be located convenient to compressor discharge.  The receivers and associated fittings shall comply with BS:5169 and BS:1123 or other approved standards.

 

                        The receivers shall be supplied complete with test certificate, safety relief valve, fusible plug, pres­sure gauge, flanged inlet and outlet connections, inspection manhole (in accordance with Clause 25.2.4 of BS:5169-1975, or similar international equivalent), screwed drain connection, automatic drain trap with balance line, drain trap isolating valve, balance.

 

                        Line isolating valve and manual drain valve, nameplate, support frame or legs, and a set of suitable foundation bolts.

 

                        As far as possible the design, manufacture and perform­ance of air receivers shall be in accordance with the following latest applicable standards :

 

                        (1)        IS:2825 – Code for unfired pressure vessels.

 

                        (2)        ASME-Sec. VIII Div.-1 Code for unfired pressure vessels.

 

                        (3)        BS:487 – Fusion welded steel air receivers.

 

                        (4)        IS:7936 – Air receivers for compressed air instal­lations.

 

2.8.16.2            Water Separators

 

                        The Bidder shall supply water separators complete with automatic drain traps. Each separator shall be rated for twice the individual compressor flow at 1 bar above maximum operation pressure.  Each water separator shall have flanged connections.

 

2.8.16.3            Drive Motor

 

                        Drive motor shall be connected to the Air compressors directly or through any suitable type of power trans­mission system.  In no case V-belt drive would be used.

 

                        The continuous motor rating (at 50°C ambient) shall be at least ten percent (10%) above the maximum load demand of the compressor in the entire operating range to take care of the system frequency variation.  Total maximum load demand shall include air compression power plus any power consumed in auxiliaries like cooling fan etc. When the driver is not directly coupled to the compressor, due account shall be made for losses in power transmission in addition to the above 10% extra margin.

 

2.8.16.4            Instruments

 

                        Each compressor shall be provided with the following instruments as a minimum:

 

                        a)         Outlet air pressure gauge                                                :           1 No.

 

                        b)         Outlet air Pressure switch                                               :           1 No.

 

                        c)         Outlet air temperature gauge                                           :           1 No.

 

                        d)         Temperature switch (to sense

                                    compressor high temperature)                                         :           1 No.

 

                        e)         Differential pressure switch across

                                    separator element                                                           :           1 No.

 

                        f)          Differential pressure switch across

                                    suction air filter                                                              :           1 No.

 

                        g)         Differential pressure switch across oil filter                       :           1 No.

 

                        h)         Temperature gauge at the inlet and

                                    outlet of oil cooler                                                          :           1 No. each

 

                        j)          Low level switch in the oil tank                                       :           1 No.

 

                        k)         Pressure gauge in the equipment cooling

                                    water supply line                                                            :           1 No.

 

                        l)          Pressure switch or Flow switch in the

                                    equipment cooling water supply line                                :           1 No.

 

                        m)        Remote (control room panel mounted) pressure indi­cator along with a pressure transmitter at the outlet header of the compressors

 

                        n)         Power On indicator light.

 

                        o)         Service hours-run meter.

 

                        p)         Load hours-run meter.

 

                        q)         Motor   overload (indicator light).

 

                        r)          Fan motor overload (indicator light)

 

                        Operation of items ‘d’, ‘j’, ‘s’ and ‘t’ shall cause the compres­sor to trip.

 

                        The bidder shall include any other instrument required to make the system safe, efficient and reliable.

 

2.8.17 AHP- Fluidising Air Blowers

Filed under: thermal power plant — Tags: — shivajichoudhury @ 6:59 am

2.8.17               Fluidising Air Blowers

 

                        Air blowers shall be designed for continuous operation with high efficiency to satisfy the system require­ments. Bidder shall furnish proper justification for selection of capacities of the blowers for various duties. 50 degree C air temperature and 100% RH shall be considered for design of capacity of air blowers.

 

                        The design shall incorporate every reasonable precau­tion for the safety of all operation and maintenance personnel.  Each blower unit should have all moving parts protected by a guard. The blowers shall be oil lubricated and water/air cooled.

 

                        The Blowers shall be constant volume/positive displace­ment type and each blower shall be provided  with suction filters, pressure relief valves with the corre­sponding vent pipe work, which shall be ducted to a safe discharge outlet, necessary isolating and non-return valves, inlet and/or outlet silencer so that blower unit can comply with the noise level require­ments.

 

                        a)         For buffer/surge hoppers, bidder shall provide a unit wise arrangement i.e. the fluidizing air for each unit shall each be supplied from a separate set of blowers of 2×100% capacity each.

 

                        b)         Each storage silos shall be provided with a 100% capacity silo aeration blowers with a common standby for all the silos.

                         

 

                        Necessary heating arrangement with a suitable bypass shall be provided at the discharge of the blowers to raise the temperature of aeration air to a temperature at least 160°C. Schemes shall also include for thermal insulation of all air pipe work from the blower outlet to the point of contact of fly ash.

 

                        All air blowers and their drives provided under this contract shall be completely interchangeable.

 

2.8.17.1            Drive Motor

 

                        Drive motor shall be connected to the Air blowers preferably directly.

 

                        The continuous motor rating (at 50°C ambient) shall be at least fifteen percent (15%) above the maximum load demand of the blower in the entire operating range to take care of system frequency variation total maximum load demand shall include air compression power plus any power consumed in auxiliaries like cooling fan etc. and transmission system losses, if any.

 

2.8.17.2            Instruments

 

                        Each silo aeration blower shall be provided with following instruments as a minimum.

 

                        (a)        Pressure gauge at the blower outlet                                  :           1 No.

 

                        (b)        Pressure gauge at the inter cooler                                    :           1 No.

 

                        (c)        Pressure switch at the blower outlet                                 :           1 No.

 

                        (d)        Pressure switch at the inter cooler                                   :           1 No.

 

                        (e)        Temperature gauge at the outlet

                                    (after air heater)                                                             :           1 No.

 

                        (f)        Temperature switch at the outlet

                                    (after air heater)                                                             :           1 No.

 

                        (g)        Pressure gauge at the equipment

                                    cooling water inlet                                                          :           1 No.

 

                        (h)        Pressure switch or flow switch at

                                    the equipment cooling water inlet                                    :           1 No.

 

                        The bidder shall include any other instrument required to make the system safe, efficient and reliable.                                                                 

 

The material of construction shall be as follows:

 

Casing

Cast Iron

Shaft

EN-8

Rotors

Cast Iron

All interconnected Piping

Galvanised steel as per IS:1239, heavy grade.  (All piping handling hot air shall be insulated to limit the surface temp. to 60°C)

 

 

December 2, 2008

2.8.18 Instrument Air Compressors and Drives

Filed under: AHP, ash handling plant, thermal power plant — Tags: — shivajichoudhury @ 7:46 am

2.8.18    Instrument Air Compressors and Drives

 

                        Air compressors shall be designed for continuous operation with high efficiency to satisfy the system requirements. Satisfactory operation in parallel shall be ensured without any uneven load sharing, undue vibration, noise etc.

 

                        The design shall incorporate every reasonable precaution for the safety of all operation and maintenance personnel.  Each compressor unit should have all moving parts protected by a guard.

 

                        The scope of supply shall include all the necessary compressed air plant complete with compressor coolers, necessary isolating and non-return valves, pressure relief valve, water separators, silencers and vent pipe work, which shall be ducted to a safe discharge outlet.

 

                        4×100%  ( 2 working + 2 stand by) capacity instrument air compressors shall be provided for both units.

 

                        The output from each set of working compressors (as applicable), expressed as free air delivered (FAD) at ambient condition, shall be sufficient to meet the instrument air requirement for one unit and silo area air requirement such as silo bag filter cleaning valve actuation. etc.   At least 10% margin shall be provided on compressor capacity over and above the maximum flow requirement. The bidder shall furnish detailed calculations of compressor sizing with the bid. A discharge pressure of  8 kg/cm2 with three steps of unloading  and design ambient of 50 degree C ambient air temp and 100% RH shall be considered for sizing of the compressors.

 

                        Compressors shall be of reciprocating oil free type.  All instrument air compressors and their drives provided under this contract shall be completely interchangeable.

 

                        The wall thickness of the cylinders shall be sufficient to withstand the maximum cylinder pressure and to permit successive re-boring without hazard.

 

 

                        Piston shall be provided with piston rings to seal the leakage of compressed air. The piston rings shall be self-lubricating material preferable graphite impregnated teflon. In case the cylinder is horizontal, suitable slipper rings shall be provided to avoid rapid wear and/or distortion of the piston ring.

 

                        Each compressor shall have an inlet filter  (dry type) unit to protect the compressor.  The filter inlet area should be large enough to ensure frequent filter changes are not required.

 

                        A crank shaft driven positive displacement lubricating pump shall be used for lubricating the bearings and any other parts needing lubrication.

 

                        Cooling water requirement, if any, shall be arranged by the bidder.

 

                        Bidder shall include an inlet and/or outlet silencer so that each compressor unit complies with the noise requirements.

 

2.8.18.1            Air Receivers

 

                        Each compressor shall be provided with an air receiver of ample size of so that delivered air pressure is kept within  ±5% of rated pressure without excessive start/stop operation in the working cycle.

 

                        Air receivers shall be located convenient to compressor discharge.  The receivers and associated fittings shall comply with BS:5169 and BS:1123 or other approved standards.

 

                        The receivers shall each be supplied complete with test certificate, safety relief valve, fusible plug, pressure gauge, flanged inlet and outlet connections, inspection manhole (in accordance with Clause 25.2.4 of BS:5169-1975, or similar international equivalent), screwed drain connection, automatic drain trap with balance line, drain trap isolating valve, balance line isolating valve and manual drain valve, nameplate, support frame or legs, and a set of suitable foundation bolts.

 

                        As far as possible the design, manufacture and performance of air receivers shall be in accordance with the following latest applicable standards :

 

                        1)         IS : 2825 – Code for unfired pressure vessels.

 

                        2)         ASME-Sec. VIII Div.-1 Code for unfired pressure vessels.

 

                        3)         BS : 487 – Fusion welded steel air receivers.

 

                        4)         IS : 7936 – Air receivers for compressed air installations.

 

2.8.18.2            Water Separators

 

                        The Bidder shall supply water separators complete with automatic drain traps.  Each separator shall be rated for twice the individual compressor flow at 1 bar above maximum operation pressure.  Each water separator shall have flanged connections.

 

2.8.18.3            Air Drying Plant

 

                        One no. each for each compressor Air drying plant shall receive compressed air saturated with moisture.  They shall be capable of operating continuously to provide reliable, moisture free compressed air supply.  Dew point of the outlet air measured at the operating pressure shall be as mentioned in the data sheet or lower throughout the working of the drying plant.

 

                        The adsorber tower shall be sized for a drying cycle (i.e. the time any particular tower is adsorbing) of period as specified (8 hours). After this period the adsorber tower will be put under reactivation operation while the other will take over the duty.

 

                        The above stated change-over from drying duty to reactivation or vice-versa shall be fully automatic with manual over ride facility.

 

                        The four way valves shall not be used in the air drying plant piping circuit for changeover facilities.

 

                        Air drying plant shall be complete with all pipings, valves, instruments and other accessories as required for safe and satisfactory operation and reactivation of the plant.  Open through system shall be used for reactivation.

 

                        Atmospheric air is filtered and is passed through the wet desiccant by a blower with the help of proper valve arrangements after heating it to required temperature by an electric heater.  This moist air is exhausted to the atmosphere. Suitable solenoid and pressure reducing valves for slow depressurisation and re-pressurisation of the adsorber tower shall be provided for such case.

 

                        The filtering media for prefilter shall be cable/candle type ceramic filter designed to withstand at least 50% of the static pressure applied as differential pressure.  Pre-filter shall be provided with isolation valves.

 

                        Quantity of desiccant shall be calculated giving the consideration to the residual moisture content at the end of regeneration cycle.  Bidder shall submit detailed calculations in support of material and quantity of desiccant offered alongwith curves (with ref. to the source of these curves) indicating variation of adsorption capacities with temp. at various R.H. at working pressure of 8 kg/cm2(g).  Bidder shall also indicate the residual moisture left in the desiccant after regeneration.  For calculating the desiccant quantity, adsorption capacity and density to be considered shall not exceed 10% and 550 kg/m3 respectively. Dew point of outlet air shall be considered as (-) 40 degree C at 1 ata pressure.

 

                        Desiccant beds shall be designed with sufficient cross-sectional area for air flow resulting in low air velocity and consequently low pressure drop.

 

                        The adsorbent material shall be supported at top and bottom by stainless steel (AISI 304) 40 mesh strainer, on mild steel plates.

 

                        Adequate free board (minimum 20% of desiccant bed depth) shall be provided to dislodge the entrained particles from the adsorber.

 

                        The adsorber tower shall be provided with suitable inspection window made of glass/pespex for observation of the adsorbent conditions and desiccant filling and removal connection.

 

                        Each air drying plant shall be complete with suitable after filters in the down stream of the adsorber towers.  After filters shall be provided with individual isolating valves, 100% standby or bypass valves.  After filter shall prevent any carry-over of desiccant particles with the effluent air stream.

 

                        For reactivation air drying plant shall be provided with the air blowers and drive of sufficient capacity and pressure for supplying air.

 

                        Dry type air filter at the suction of blower shall be provided.

 

                        Heater shall be used to heat the air upto the required temp. for the purpose of reactivation of wet desiccant bed. Suitable temp. and pressure indication shall be provided at the outlet of the heater shell.  The heater shall be fabricated as per IS:2825 or approved equal.  The heater shall be thermostatically controlled, electric type and shall preferably of flanged type so that replacement burnt out heating element or other maintenance work is easy.

 

                        All pressure vessels such as moisture separator, prefilter and after filter casings, adsorber towers etc. shall be designed as per IS:2825 or approved equal.  All vessels shall be Class-II type as per the said standard.  Adequate provisions for manhole/handhole, relief valve, draining trap station shall be made.  Internal surfaces of all the vessels shall be suitably protected against corrosion and rusting.

 

Material of construction shall be as follows:

 

Compressor

To suit service condition and as per relevant codes/standards

Air receiver

IS:226/IS:2002/IS:2062

Inter Cooler and After Cooler

 

Tube

S.S.

Shell

SA 285 Gr. C

Air drying plant

 

Retention mesh for Silica Gel and other components coming in contact with moisture.

SS

 

2.8.18.4            Drive Motor

 

                        Drive motor shall be connected to the air compressors directly or through any suitable type of power transmission system.

 

                        The continuous motor rating (at 50°C) shall be at least fifteen per cent (15%) above the maximum load demand of the compressor in the entire operating range to take care of the system frequency variation.  Total maximum load demand shall include air compression power plus any power consumed in auxiliaries like cooling fan etc.  When the driver is not directly coupled to the compressor, due account shall be made for losses in power transmission in addition to the above 10% extra margin.

 

2.8.18.5            Instruments

 

                        Each Compressor shall be provided with the following instruments as a minimum:

 

                        (i)         Pressure Gauges

 

                        a)         with each air receiver for air pressure                              :           1 No.

 

                        b)         after each stage (LP & HP) for air pressure                     :           1 No.

 

                        c)         at the lubricating oil inlet for oil pressure                          :           1 No.

 

                        d)         at the prefilter (air drying plant) inlet and

                                    outlet for air pressure                                                     :    1 No. each

 

                        e)         at the adsorber tower inlet & outlet for

                                    air pressure                                                                   :    1 No. each

 

                        f)          at the after-filter (air drying plant) 

                                    outlet for air pressure                                                     :           1 No.

 

                        g)         at the blower (air drying plant) outlet

                                    for air pressure                                                              :           1 No.

 

                        h)         with the air receivers on instrument

                                    air line near each unit for air pressure                              :           1 No.

 

                        j)          at the cooling water inlet to each

                                    compressor unit for C.W. pressure                                  :           1 No.

                        k)         at the instrument air ring header

                                    for air pressure                                                              :           1 No.

 

                        l)          at the inter-cooler outlet for C.W. pressure                       :           1 No.

 

                        m)        before air receiver for each compressor

                                    for C.W. pressure                                                          :           1 No.

 

                        n)         at the after-cooler inlet for C.W. pressure                        :           1 No.

 

 

                        (ii)        Temperature Gauges

 

                        a)         after each stage (LP & HP) for

                                    air temperature                                                              :    1 No. each

 

                        b)         at the C.W. outlet of each cylinder

                                    for C.W. temperature                                                     :           1 No.

 

                        c)         at the inlet of HP cylinder for

                                    C.W. temperature                                                          :           1 No.

 

                        d)         at the after-cooler outlet for

                                    C.W. temperature                                                          :           1 No.

 

                        e)         at the after-cooler outlet for air

                                    temperature                                                                   :           1 No.

 

                        f)          with each air receiver for air temperature                         :           1 No.

 

                        g)         at the adsorber tower inlet & outlet

                                    for air temperature                                                         :           1 No.

 

                        h)         at the outlet of heater for air drying

                                    plant for air temperature                                                 :           1 No.

 

                        i)          at the lubricating oil inlet for

                                    oil temperature                                                              :           1 No.

 

                        j)          at the cooling water inlet to each

                                    compressor unit for C.W. temperature                             :           1 No.

 

                        k)         at the lubricating oil in crank case

                                    for oil temperature                                                         :           1 No.

 

 

                        (iii)       Pressure Switches

 

                        a)         with each air receivers

 

                                    i)          for air pressure high                                           :           1 No.

 

                                    ii)         for air pressure low                                            :           1 No.

 

                                    iii)        for load/unload                                                  :   1No. each

 

                                    iv)        for start/stop                                                      :   1 No. each

 

                        b)         at the lubricating oil inlet for oil pressure low                    :           1 No.

 

                        c)         at the compressor discharge

 

                                    -           for air pressure high                                           :           1 No.

                                    -           for air pressure low                                            :           1 No.

 

                        d)         at the air drying after filter outlet for

                                    instrument air pressure low                                             :           1 No.   

 

                        e)         at the instrument air ring header

                                    for instrument air pressure low                                        :           1 No.

 

 

                        (iv)       Temperature Switches

 

                        a)         with the cylinder jacket for water

                                    temperature high                                                            :           1 No.

 

                        b)         before the after-cooler for air

                                    temperature high                                                            :           1 No.

 

                        c)         after the after-cooler for air

                                    temperature high                                                            :           1 No.

 

                        d)         after the inter-cooler for air

                                    temperature high                                                            :           1 No.

 

                        e)         with the reactivation air dryer for

                                    reactivation air temperature low.                                     :           1 No.

 

 

                        (v)        Flow Indicators

 

                        a)         at the cylinder C.W. outlet for C.W. flow                        :           1 No.

 

                        b)         at the after-cooler outlet for C.W. flow                            :           1 No.

 

                        c)         at the inter-cooler outlet for C.W. flow                            :           1 No.

 

                        d)         at the lubricating oil cooler outlet

                                    for C.W. flow                                                                :           1 No.

 

                        e)         at the cooling water supply line to

                                    Air Compressor for C.W. flow                                        :           1 No.

 

 

                        (vi)       Level Gauges

 

                        a)         at the inter-cooler moisture separator                               :           1 No.

 

                        b)         at the after-cooler moisture separator                               :           1 No.

 

                        c)         at each air receiver.                                                        :           1 No.

                       

                        (vii)      Vacuum gauge at the suction filter                                   :           1 No.

 

                        (viii)     Flow switch in the cooling water supply

                                    line to air compressor unit to trip the

                                    compressor in case of low flow of water.                         :           1 No.

 

                        (ix)       Indicating type flow switch in the

                                    instrument air line to air receiver for

                                    each unit to alarm high flow due to leakage.                     :           1 No.

 

                        (x)        Differential pressure gauge across oil filter.                       :           1 No.

 

                        The bidder shall include any other instrument required to make the system safe, efficient and reliable.

 

2.8.18.6                        Gear Boxes

 

Gear boxes containing helical gears, totally enclosed and lubricated shall be used for speed reduction between motor drives and driven Equipments. (i.e. Compressors, blowers, clinker grinders, combined ash slurry disposal pumps, scrapper conveyors, etc.)

 

Gear boxes shall be totally enclosed and oil lubricated type. Positive lubrication shall be provided to all the bearings and particularly to the working surface of the gear teeth.

 

                        The gear unit shall be specifically designed for continuous service at the speeds required by the application. Precision and accuracy of manufacture is essential to minimise problems of vibration, impact stresses, noise distortions and lubrication.

 

                        Dynamically balanced, helical gears shall be used.

 

            i)          Casing

 

a)         The gearing shall be enclosed in an oil and dust proof gear case made of closed grained cast iron or fabricated steel.

 

b)         The gear case shall be horizontally split and stress relieved before machining. The faces of adjoining sections shall be accurately machined to provide oil tight joints. Oil level gauges, drain, fill vent, thermometer, dipstick and other required connections equipped with approved mountings, valves and fittings shall be furnished for the gear casing.

 

c)         The housing shall be generously proportioned and of rigid construction to provide permanent alignment of rotating parts and protection from possible external vibration. The arrangement shall be such that it will be possible to lift gear case cover without disturbing the alignment of shaft, gear and pinion.

 

                        The gear box shall be provided with suitable bearings of conservative design to meet the worst duties under transients.

 

            ii)         Rating of Gear Box

 

a)         Gear box shall be designed for heavy shock loads and while selecting a gear box a service factor of minimum 2.0 shall be considered.

 

b)         The nominal mechanical KW rating of each gear box shall not be less than the name plate KW rating of the selected drive motor.

 

c)         Thermal rating of each speed reduction gear box at 500C ambient temperature shall not be less than the name plate KW rating of the selected drive motor.

 

d)         For cooling of gear box, in case thermal capacity without auxiliary fan is not sufficient to meet the thermal rating of gear box, necessary auxiliary cooling fan shall be provided. Cooling coil for this purpose is not acceptable.

 

e)         The selection of gear box shall be subject to Owner’s approval. The Bidder shall furnish necessary calculations and selection charts for this purpose for Owner’s review and approval.

 

2.8.19               Wetting Head

                        Adequately sized wetting head shall be provided above collector tank for wetting the dry fly ash and separating it from convey­ing air, if any.

 

                        The wetting head shall be provided with a water supply of sufficient quantity and pressure for feeding the nozzles that will produce fog spray of water, ensuring rapid wetting of the incoming ash.

 

                        Nozzles shall be so directed as to prevent spray from entering the ash discharge pipe.

 

                        The bidder shall elaborate as to have water vapour generated by the rise in water temperature shall be prevented from rising from the wetting head into the discharge chute to avoid the possibility of dry ash discharge pipe chute blockage.

 

                        Wetting head shall be compact in design and provisions shall be made for easy replacement of nozzles.  Flanged connections shall be provided for all inlet and outlet connections of the wetting head.

 

Material of construction shall be as follows:

 

(a) Body

Close grained 2% Nickel cast iron minimum hardness 250 BHN.

(b) Nozzle

Body of MS/Cast Iron and replaceable tip of Anti corrosion tool steel or stainless steel of hard­ness 500-550 BHN. OR Ceramic material.

 

2.8.20               Collector Tanks

 

                        The collector tank shall be located below the wetting tank and serve the purpose to separate and vent out air  and  discharg­ing the ash slurry to the combined ash disposal sump through pipe lines.  This will also serve the purpose of separating and venting out the entrapped air discharged by wetting head and before discharging the entrapped air into atmos­phere, it shall be passed through an air washer to achieve a sustained outlet dust emission of 50 Mg/Nm3 (Max.) with the ash handling system operating at de­signed capacity.  The dust emission figure shall be guaranteed.

 

                          The collector tank shall be located at an elevation which will provide sufficient static head to overcome frictional and other losses in the gravity flow dis­charge line upto ash slurry sump.

 

                        For maintenance purposes suitable stair case, mainte­nance platform, walkway with handrails at necessary levels shall be provided.

 

                        The sizing of collector tank, inlet/outlet connections etc. shall be corresponding to the maximum anticipated discharge flow requirements.  The collector tank shall be complete with drain, overflow and vent pipe connec­tions alongwith pipes and requisite size and lengths.

 

                        The tank shall be internally lined with alloy C.I. liners of thickness not less than 20 mm.

 

The material of construction shall be as follows:

                       

Tank

Tested quality, M.S. of mini­mum 10 mm thickness, as per IS:2062.

Baffle

Tested quality M.S., of mini­mum 12 mm thickness, as per IS:2062.

Liners

Alloy C.I. (300-350 BHN), 20 mm, thick minimum.

 

 

2.8.21 Bag Filters

Filed under: thermal power plant — Tags: — shivajichoudhury @ 7:44 am

2.8.21               Bag Filters

 

                        The bag filter unit shall be placed above all the buffer/ interme­diate hoppers, and the main ash storage silos. In case of storage silos and buffer/ intermediate hoppers for pressure conveying system, the bidder should provide exhaust fans to assist venting.

 

                        Because of the stringent duty conditions, it should be possible to carry out the maintenance and replacement of the bags without affecting the performance of the system.

 

                        The Bidder shall justify in his bid, the air to cloth ratio selected, the bag material, the ability to with­stand the vacuum, pressure and temperature, the mainte­nance and replacement procedures of the damaged bags.

 

                        The performance of the bag filter shall not get affect­ed with 10% of the bags plugged.  This condition shall be demonstrated by the Contractor at site under actual working conditions.

 

                        The bag filter unit shall be designed to achieve as sustained outlet dust emission of 50 mg/NM3 (maximum).  The dust emission figure shall be guaranteed.

 

                        All bag filters and fans shall be installed under cover, and be protected from all potential adverse weather conditions.

 

                        All bag filters shall be supplied complete with auto­matic bag filter cleaning equipment, details of which shall be included in bid.

 

2.8.22 Dry Fly Ash Storage Silos

Filed under: thermal power plant — Tags: — shivajichoudhury @ 7:42 am

2.8.22               Dry Fly Ash Storage Silos

 

                        2 Nos. storage silos each to store 1000m3 of dry fly ash with adequate margins shall be provided. Storage silos shall be of flat/conical bottom type with the provision of air slides/fluidising pads at the bottom. Storage silos shall be provided to store precipitator fly ash with adequate air space.  This silo shall be used to collect dry fly ash for the purpose of sale. It shall have facilities for dry ash unloading into cov­ered road tankers and conditioned fly ash in open road tankers. The silos shall be R.C.C. constructed.

    

                        Each dry fly ash storage silo shall be provided with following arrangement for unloading the fly ash.

 

                        (a)        A retractable chute alongwith rotary feeder for unload­ing  the dry fly ash into closed road tankers at a rate of 120 T/hr. max.

 

                        (b)        A ash dust conditioner alongwith feeder for load­ing the conditioned ash into open road tankers at a rate of 40-120 T/hr.  The water content in the conditioned ash shall vary between 0 – 15 %

 

                        (c)        Two blanked connections along with isolation valves shall also be provided in the silo for future installa­tion of pneumatic equipment for transportation of a dry ash to third party and for installation of equipment to slurrify the dry ash to dispose off it through ash disposal system.

 

                        The storage silo shall be designed to provide a clear access of 5.5m for a road tanker to come under the silo and receive the ash from the retractable chutes. To facilitate locating these chutes over the road tanker opening, it shall be possible to move the chute in all directions in the horizontal plane. It may be noted that unloading system from Silo shall be suitable for both rail wagon unloading and closed tanker/open truck unloading.

 

                        Each retractable chute shall include a shut off device at the chute outlet, a level probe to determine the level of ash within the road tanker, dedusting and vent air systems, and a motor operated winch system to lower/raise the chute.

 

                        Each storage silo shall be provided with a separate and dedicated floor aeration system.  This aeration should only be required during silo unloading and should not be in operation during storage periods.

 

                        The silo aeration system shall be supplied by con­stant volume blowers. Any manifolds employed for air distribution in the aeration system shall be fitted with blank flanges at the mani­fold ends, to facilitate maintenance requirements.

 

                        A suitable dust suppression system at various levels of the silo shall be provided, if required.

 

                        The pressure/vacuum relief valves in the storage silos shall be provided.

 

                        Bag filters shall be provided on the storage silos for cleaning the aeration and displaced air before venting out.  The Bidders should provide exhaust fans to assist venting. Bag filters and fans shall be installed under cover, and the protected from all potential adverse weather conditions.

 

                        The dust loading from the outlet of the bag filters shall not exceed 50 mg/Nm3 under any operating condi­tion with 10 per cent bags plugged.  Bidders shall justify the selected air to cloth ratio of the bag filters.  The Bidders shall also supply details on how the air flow into and out of, the storage silos is balanced during different operating conditions. 

 

                        The provision of a proven dust collection system in the storage silos that separate out bulk of the ash from the conveying air shall be provided before the air is extracted through the bag filters.

 

2.8.22.1            Instruments

 

                        Each silo shall be provided with following instruments as a minimum :

 

                        a)         Silo ash level switches (High and Low)                            :           1 No.

 

                        b)         Level switch with the telescopic chutes

                                    (meant for unloading into closed tankers)                         :           1 No.

 

                        c)         Differential pressure gauge across the bag filter                 :           1 No.

 

                        d)         Differential pressure switch across the bag filter                :           1 No.

 

                        e)         Pressure gauge at the inlet of the bag filter                       :           1 No.

 

                        f)          Differential pressure gauge across the vent filter               :           1 No.

 

                        g)         Differential pressure switch across the vent filter              :           1 No.

 

                        h)         Pressure gauge at the inlet of the vent filter.                     :           1 No.

 

                        The bidder shall include any other instrument required to make the system safe, efficient and reliable.

 

2.8.23 Water and Air Piping, Fitting and Accessories

Filed under: thermal power plant — Tags: — shivajichoudhury @ 7:40 am

2.8.23               Water and Air Piping, Fitting and Accessories:

 

                        All required water and air pipework including all instrument impulse piping and fitting for complete DAETP shall be provided as specified.

 

                        All piping system shall be capable of withstanding the maximum pressure (pump shut off) in the corresponding line at the relevant temperatures.

 

                        All piping system shall be properly designed to take care of water hammer/pressure surges which may arise during operation of the system. 

 

                        All piping shall be provided with vents at the highest points and drains at the lowest points alongwith vent valves and drain cocks. Vents shall not be less than 15mm in size. Drains shall not be less than 25 mm size.

 

                        Bends, loops, off sets, expansion or flexible joints shall be used as required in order to prevent over­stressing of the piping system due to thermal movements and to provide adequate flexibility.

 

                        The design, supply and installation of all pipe sup­ports and hangers including pipe clamps, turn buckles, hanger rods, auxiliary steel etc. shall be furnished.  All bolting materials companion flanges, nuts gaskets etc. as required in the piping system and at all terminal points shall be furnished.

 

                        All piping shall be routed so as to avoid interference with other pipes and their hangers and supports, elec­trical cable trays, ventilation ducting structural members, equipment etc.  Adequate clearance shall be ensured with respect to the above to accommodate pipe movement.

 

                        The piping shall be arranged to provide clearance for the removal of equipment requiring maintenance and for easy access to valves and other piping accessories required for operation and maintenance.

 

                        Piping shall generally be routed above ground but where specifically indicated/approved by the Engineer the pipes may be arranged in trenches or buried.  Bidder shall provide either coal tar and Bitumen tapes on conventional coat and wrap system for corrosion protec­tion of buried piping as per relevant codes and stand­ards.

 

                        Overhead piping shall have a normal minimum vertical clearance of 3 metres above walk ways and working areas and 6 metres above roadways.

 

The following line velocities shall be considered for estimating the line sizes of water pipes and Air Pipes:

 

 

                        ————————————————————————————————–

                        Service                             Velocity, M/Sec

                        ————————————————————————————————–

                                                                    Pipe size              Pipe size                Pipe size

                                                                    size below           of 50 to                  of 200 mm

                                                                    50 mm                150 mm                 and above

                        ————————————————————————————————–

                        a)   Water pump                    06-0.9                 1.2-1.5                   1.2-1.5

                              Suction

 

                        b)   Water Pump                    0.9-1.8                1.5-2.4                   1.8-2.8

                              Discharge

 

                        c)   Compressed                    15-20                  15-20                     20-30

                              air below

                              2 Kg/cm2(g)

 

                        d)   Compressed                    20-30                  20-25                     25-35

                              air, 2 Kg/cm2 (g)

                              & above

                        ————————————————————————————————–

                        Note

 

                        1.         Pipe Size in pump suction side shall be at least one pipe size larger than the corresponding pump discharge connec­tion.

 

                        2.         The proposed sizes of the water and air pipes shall be submitted.

 

                        The pipe supports shall be spaced as follows.

 

                        Pipe size(NB)    25        50        100       150       200       300       400       500

                        Spacing in         2.1       3.0       4.3       5.2       5.8       7.8       8.2       9.8

                        metre   

                       

2.8.23.1                                         Water and Air Piping,

Fittings and Accessories

1.0

Type of Pipes

a) Upto & including150 NB

MS, ERW pipes to IS:1239 Heavy grade

 

 

b) 200 NB to 450 NB

MS ERW to IS 3589.

 

 

 

OR

 

 

SAIL or equal make

ERW commercial quality pipes.

 

 

c) 500 NB and above

Rolled and welded from MS plate to IS:226 Dimensional toler­ance as per IS:3589.

 

 

 

OR

 

 

 

SAIL OR Equal make

 

 

 

spiral welded pipes. 

 

 

 

Dimensional toler­ance as per IS:3589.

2.0

Pipe SIzes

As required.

 

3.0

Thickness of Pipes

a) Pipe specs. as per IS:1239

Pipe thickness shall be of Heavy grade.

 

 

b) Pipe spec. as per IS:3589(ERW)

Min 6.35mm thick for 200 NB to 400 NB size and Min. 7.14 mm thick for 450 NB size.

4.0

Type of Line joints.

 

 

 

 

a) 50 NB and below

Socket welded to ANSI:B16.11.

 

 

b) 65 NB and above.

Butt welded to ANSI:B16.25.

5.0

Quantity

As required

 

6.0

Fittings (Bends)

 

 

 

 

a) For sizes upto& including65NB

3D radius bends and material same as that of parent pipe.

 

 

b) For sizes 80 NB to 300 NB

 SR & LR elbow and material same as that of parent pipe

 

 

c) 350 NB & above.

Miter bends with Miter angle not exceeding 22.5°.  Material shall be same as that of parent pipe and dimensional toler­ance shall be as per BS : 534.

7.0

Flanges

Slip on flat face type with drilled and pressure rating as per valve and other specialities. Material of construction shall be IS:226 upto 20 MM thickness and IS:2062 for higher thickness.

8.0

Bolts

As per IS:1367 Cl.4.6 or ASTM-A-307-Gr.B.

9.0

Nuts

As per IS:1367 Cl.4.0 or ASTM A-307 Gr. B.

10.

Gaskets

Wire inserted Red rubber.  Thickness shall be 1.6 mm for sizes upto and including 250 NB and 3.2 mm for higher sizes.

II.  Air Pipes

 

1.0

Type of Pipe

a) ERW pipe as per IS:1239, heavy grade with galvanising as per IS:4736 for pipes  upto & including 150 NB. For pipes of sizes above 150 NB it shall be as per Cl. I (1.0, b) & Cl. No. I (3 b) above.

 

 

b) For compressed air piping for instru­ment and control loops, bulk heads, the following standard shall be adopted

 

 

i)                 For sizes25 NB and including 50 NB.

ii)                For sizes below 25 NB

Seamless Red Brass ASTM B43 Sch.40.

 

 

 

 

Seamless Copper to ASTM  -75

2.0

Pipe Sizes

As required

3.0

Thickness of pipes

For pipe size upto & including 150 NB pipe thickness shall be of heavy grade as per IS:1239 and for pipes of higher sizes, the thickness shall be as per clause No. I (3.0) b & c on page-5 mentioned above for water pipes.

4.0

Type of Line joints

(a) 65 NB and below

Screwed

 

 

(b) 80 NB and above

Sleeve welded . However valve etc. shall be IS:226 upto 20 mm thickness and is:2062 for higher thickness.

 

5.0

Quantity

As required.

 

6.0

Fittings/ (Elbows)

As per ASTM-A-234 Gr. WPB (GI)

7.0

Flanges

Raised face type G.I. screwed and pressure rating as per valve and other specialities.   Material of construction shall be IS:226 upto 20 mm thickness and IS:2062 for higher thickness.

8.0

Bolts, nuts & Gaskets.

Same as for water pipes

 

2.8.24 Water and Air Line Valves and Special

Filed under: thermal power plant — Tags: — shivajichoudhury @ 7:38 am

2.8.24               Water and Air Line Valves and Specialities

 

                        All valve shall be suitable for the service conditions i.e. Flow, temperature and pressure under which these are required to operate and those performing similar duties shall be interchangeable, with one another unless otherwise approved. All valves and connections shall be suitably protected to prevent damage and entry of dirt, till erected.

 

                        End to End dimensions shall be in accordance to ANSIB16.10 or as per codes to which they conform to.

 

                        All manually operated valves of all sizes 350 NB and above shall be provided with gear operator of proven quality, reputed make and conforming to internationally accepted standard.

 

                        All valves shall be fitted with open/close position indicators.

 

                        All valves shall be provided with hand wheels, extension spindles and floor stands or any other arrangement wherever required so that these can be operated manually with ease by a single operator from the nearest operat­ing floor either at a lower or higher elevation as the case may be. Wherever necessary for safety purpose, locking devices shall be furnished with valves.

 

                        All Gate and Globe valves shall be of outside screw and yoke (OS&Y) type and provided with back seat to permit repacking with valves in operation.

 

                        The actuator operated valves shall be designed on the basis of the following:

    

                        a)         The internal parts shall be suitable to support the stresses caused by the actuator.

    

                        b)         The valve actuator unit shall be suitably stiff so as not to cause vibrations, misalignment etc.

 

                        c)         Motorised Valves shall be provided with hand operating gear, hand wheel and clutching and declutching arrange­ment.

 

                        The size of all valves shall be the same as that of parent pipe.

 

                        The end connections shall comply with the following:

 

                        -           Socket welding (SW)                 -           ANSI B16.11

                        -           Butt welding (BW)                     -           ANSI B16.25.

                        -           Threaded (SC)                          -           ANSI B2.1

                        -           Flanged (FL)                             -           ANSI B16.5.

 

                        Gate valves shall be used for isolation purposes, Globe valves shall be used for regulation purpose, check valves shall be used for non-return service, and plug valves shall be used for isolation purpose in those lines where quick opening and closing is required in the system.

 

                        Double flanged or wafer type butterfly valves of low leakage rate conforming to AWWA-C-504, BS:5155 or any other approval equivalent latest standard edition can also be used for isolation, quick isolation and regula­tion purposes.

 

                        Material of construction shall be as follows:

 

For sizes below 50 mm and working pressure or shut off pressure (whichever is  higher) is upto 15 Kg/cm2(g)/ (upto 10 Kg/cm2(g) for Plug valves)

 

Body/Wedge/Disc

 

Gun Metal

 

 

Trim & Stem

 

Gun Metal

 

For sizes 50 mm and above and working pressure or shut off pressure (whichever is higher) upto 15 Kg/cm2(g).

 

Body/Wedge/Disc

 

C.I. to IS 210 Gr. FG 220

 

 

Trim & Stem

 

Brass/ Gun Metal

 

For all sizes and working pressure or shut off pressure (which ever is higher) is   above 15 Kg/cm2(g) (Above 10Kg/cm2 for plug valves).

 

Body/Wedge/Disc

 

Cast/Forged carbon steel

 

 

Wedge/Disc/Plug

 

Cast carbon steel with 13% Cr

 

 

Trim and Stem

 

Stainless steel

 

 

2.8.25 Ash Slurry Disposal Pipes and Valves

Filed under: thermal power plant — Tags: — shivajichoudhury @ 7:35 am

2.8.25               Ash  Slurry Disposal Pipes and Valves

 

                        Combined Ash Slurry Disposal Pipes

 

                        The ash slurry disposal piping and associated fittings starting from slurry disposal pumps suction upto ash slurry dump area outlet to ash slurry sump shall be furnished complete with all couplings, steel supports, hangers, clamps, support, inserts, nuts, bolts, gaskets etc.

 

                        The ash slurry disposal pipe diameter should be designed considering slurry veloci­ty of 2.8M/Sec. (Max) in the pipe.

 

                        The minimum wall thickness of slurry piping shall be 9.52 mm  (minimum)

 

                        The routing of the ash slurry disposal pipes shall be indicated in the drawings enclosed with the bids. The pipelines shall be provided with adequately sized drain connections with blind flanges as per the final layout requirements.

 

                        Bidder shall conduct line surge studies for the ash disposal pipelines. Suitable arrangements as required to protect the system based on approved line surge studies shall be included in Bidder’s scope.

 

The ash concentration in slurry (W/W) shall be for 25% w/w for bottom and combined bottom and fly ash. For fly ash the same shall be 30% w/w.

 

2.8.25.1            Fittings

 

                        All fittings (bends, elbows, laterals & spool pieces etc.) used in ash slurry disposal piping  upto ash dyke shall be basalt lined/ Ni hard with flanged ends or integral wear back type alloy C.I. fittings.  Minimum thickness of wear back shall be twice the pipe wall thickness.

 

                        These fittings shall be as per good engineering practice and of large radius (Min. 3D) con­struction.

 

                        Alloy C.I. or Basalt lined spool pieces (as the case may be) of minimum 1.5 metre length shall be provided at the discharge of every fitting having an angle of 45°.and more.

 

                        All fittings (bends, elbows, laterals & spool pieces etc.) used in ash slurry disposal piping over ash dyke shall be M.S. fabricated with flanged ends with minimum 20 mm thick integral wear back.

 

2.8.25.2            Couplings

 

                        For ease of rotation and replacement of ash slurry disposal pipes at regular intervals of time for maintenance purpose, sleeve type couplings shall be provided.

 

                        Straight length of pipes without any intermediate coupling shall not exceed 50 metres.  It shall be possible to replace or rotate (as applicable) any fitting and any particular spool or pipe during maintenance without unduly disturbing neighbour­ing healthy joints and pipe spools. 

 

                        The coupling shall be capable of taking a minimum of 2° angular deflection and sufficient gap between ends of pipes at couplings shall be provided to take care of expansion in piping.

 

The thickness of coupling sleeve shall be 9 mm (min.)

 

                        The material of construction shall be as follows:

                       

Ash slurry line

ERW steel pipes to SAIL commercial Quality/API-5L Gr.B/IS:3589

 

Ii.   Pipe Fittings (Bends, Elbows, Laterals And Spool Pieces Etc.)

1.0

Material and Hardness

:

i)Upto Ash dyke

Ni hard/chromo alloy C.I. or equivalent of minimum 400 BHN. Integral wear back of minimum 20 mm thickness.

 

 

 

OR

 

 

 

 

 

20 mm thick cast basalt lined MS fittings (MS shell of 6 mm thickness)

 

 

 

 

Hardness : 8 mhos (minimum)

 

 

 

 

 

Bending strength : 300 Kg/cm2 (minimum)

 

 

 

 

 

Compressive strength : 4500 Kg/cm2 (minimum)

 

 

 

 

 

 

 

 

 

 

 

  ii) Over Ash dyke

 

 

 

 

 

MS fabricated with minimum 20 mm thick integral wear back. The pipe thickness of fittings shall be 10 mm.

III.

Couplings

 

 

 

 

1.0

Type

:

Sleeve type couplings with minimum9.0 mm thick sleeve.

2.0

Material of Construction

 

 

 

 

 

 

 

 

 

 

2.1

Sleeve

:

Carbon Steel to ASTM A-36/BS EN 10025:1993 Grade S:275/355

2.2

Flanges/End rings

:

Carbon Steel to ASTM A-108. Steel end rings shall be formed from special hot rolled section bar, Free from circumferential welds.

2.3

Gasket

 

 

 

 

 

(i) Material

:

EDPM to BS:2494:1990 Type D/Isoprene/Buna-N/Neoprene

 

 

 

 

 

Test Procedure

 

(ii) Properties

:

(a) Durometer hardness: Shore ‘A’ points

50 to 70

ASTM D-2240

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(b) Tensile strength min.ultimate:

1300 psi(min.)

ASTM D-412

2.4

Nuts & Bolts

:

Hot dip galvanised/spray galvanised as per IS:4759. Bolts, nuts and washers should be of similar material to those used for coupling housings/sleeves to minimise the possibility of galvanic corrosion

Older Posts »

Theme: Silver is the New Black. Blog at WordPress.com.

Follow

Get every new post delivered to your Inbox.